Suppression engineered for the interior of battery cabinets and containers — addressing re-ignition after discharge, the failure mode conventional clean-agent units do not cover.
Designed for the interior of battery energy storage cabinets and containers. Unlike conventional clean-agent units that rely on stored cylinder pressure, this unit uses a pump set as the pressure source: FK-5-1-12 agent is pressurized and then atomized through misting nozzles. The atomized agent continuously removes heat generated by cell reactions, preventing heat accumulation and re-ignition — a failure mode that other products in this category do not address.
When the PACK-level composite detector confirms a fire condition, the suppression control panel starts the pump set and opens the cluster solenoid valve. Atomized FK-5-1-12 is injected into the affected battery modules; discharge repeats in programmed pulses to suppress propagation. If thermal runaway is not contained after full agent discharge, the secondary water-mist circuit can be activated to flood the affected cluster with fire water.
| Parameter | YF-F-100W-ZHTA | YF-F-200W-ZHTA |
|---|---|---|
| Rated voltage | 220 V | 220 V |
| Rated power | 1.8 kW | — |
| Head | 54 m | — |
| Flow rate | 4.0 m³/h | — |
| Speed | 2,900 rpm | — |
| Overall dimensions (L×W×H) | 400 × 400 × 1450 mm | 450 × 450 × 1700 mm |
| Controller operating temperature | −20 °C to +80 °C | −20 °C to +80 °C |
| Motor rated current | 68 A (24 V) | — |
| Extinguishing agent | FK-5-1-12 | FK-5-1-12 |
A pre-engineered unit for confined spaces. Self-contained: the agent cylinder and the entire system are installed inside the protected rack or cabinet. Compared with other extinguishing products it offers a smaller footprint, easier installation, minimal agent loss and faster extinguishing. An ideal solution for protecting small spaces, and an effective supplement to — or replacement for — conventional extinguishing units.
| Parameter | Value |
|---|---|
| Type | Temperature-actuated / electrically actuated / dual-actuated / intelligent |
| Cylinder charge | 2 kg / 3 kg / 6 kg |
| Extinguishing agent | HFC-227ea / FK-5-1-12 |
| Actuation condition | ≥ 68 °C / DC 24 V / +68 °C & 24 V / linked · auto · manual |
| Rack size | 1U / 2U / 4U |
| Discharge time | ≤ 10 s |
| Storage pressure | 1.6 MPa / 1.2 MPa |
| Ambient temperature | 0 °C to +50 °C (HFC-227ea) / −10 °C to +50 °C (FK-5-1-12) |
| Fill density | ≤ 1120 kg/m³ (HFC-227ea) / ≤ 1400 kg/m³ (FK-5-1-12) |
Y*2.4-1.6-W-ZHTA · JJQR-*-C-1.5×2/1.2-ZHTA · JJQR-*-W/C-1.5×2/1.2-ZHTA · JJQR-*-Z-1.5×2/1.2-ZHTA · Y*4-1.2-W-ZHTA · JJQR-*-C-6/1.2-ZHTA · JJQR-*-W-6/1.2-ZHTA
* denotes Q (HFC-227ea) or F (FK-5-1-12).
Send us your battery chemistry, rack layout and target market.